Worked example

For a 125 A bus and 125 A main, the ceiling is 150 A. A 16 A continuous source contributes 20 A. The total is 145 A, leaving 5 A under the formula for the one-end example.

Center-feed geometry needs to be verified from the actual panel documentation. Select the appropriate placement in the worksheet. A supply-side tap is evaluated under 705.11 and requires separate utility, equipment and service-conductor review.

Calculation method

  1. Read the busbar and main separately

    The panel label supplies the busbar rating. The protective device feeding the bus can be a different size. Multiply the bus rating by 1.20 to get the ceiling for this method.

  2. Choose the input basis

    The 2023 text uses 125% of the power-source output circuit current plus the main protective device. Using source breaker handles in place of their adjusted current values is a conservative screen when the devices cover the source load.

  3. Confirm the layout

    NEC 2023 places the opposite-end method in 705.12(B)(2), formerly 705.12(B)(3)(2) in 2020. The center-fed dwelling option is 705.12(B)(4) and uses one end of the bus.

Check the panel listing, Article 220 loads and the required label at the power source connection. Supply-side connections follow 705.11. An approved EMS or another 705.12 method needs its own documented design.

Common questions

Can I use the center-fed choice for connections at both ends?

The modeled 705.12(B)(4) configuration uses one end of a center-fed dwelling panel. Choose the other-placement mode for an alternative review.

Where was the 120% center-fed rule numbered in the 2020 edition?

It appeared under 705.12(B)(3)(4) in the 2020 structure. The 2023 edition places the option in 705.12(B)(4).