Worked example
Each unit has 6 A maximum continuous AC output. The 30 A branch gives 30 ÷ 1.25 = 24 A of budget. Four units reach that value and match the listed 10 AWG branch count.
The same microinverter can connect multiple DC modules. Count microinverter units on the AC branch and check the exact trunk kit and connector. Adjust for site conditions and verify the distribution equipment and wiring permit the selected breaker.
Calculation method
Use AC continuous current per microinverter
Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.
Check the trunk and branch
Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.
Check the combiner separately
Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.
Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.
Common questions
What is the calculated HMS-1600 count with a 20 A budget?
An electrical budget of 16 A supports two 6 A units. Confirm the 20 A trunk and unit combination in the specific instructions.
Does each panel connected to an HMS-1600 count as an AC inverter?
Count each HMS-1600 once on the AC branch. Its DC inputs connect multiple PV modules.